Mastco's
Monitoring Systems
|

Contact
us to receive a
full color brochure on our line
of Monitoring equipment
-or-
Download brochure in
pdf format
(1020KB)
Viewing
this document
requires
acrobat reader.
Click on the Icon below in order to download the reader
which is
compatible with your system.

info@mastco.net
|
|
Developed for the Protection, Monitoring and Management
of Humanities most Priceless Resources

Mastco's
Temperature Monitoring System was designed with traceability
and validation throughout. Audible and visual alarms,
archiving functions, tamperproof settings and multiple
printouts are just some of our features.
Mastco's
monitoring systems include distinctive features that managers,
supervisors, and technicians need but find lacking in
other makes of temperature monitors. All products are
specifically designed with the customer in mind and to
conform to all regulatory requirements.
The essential prerequisites of a temperature monitoring
system are ease of viewing, ease of operation, management,
and essentially reliability.
Our three key Product lines are AlarmLog,
ScanLog, and the MSM
Our
encapsulated PTFE temperature probes come standard with
most of Mastco's Monitors including AlarmLogs and DuaLogs!
The
Mastco team is extremely proud of our temperature monitoring
systems and is convinced you will find one
perfect for your needs.
Mastco's temperature range of -200° C to +200° C
(-328° F to +392° F) is the best in the industry.
We
also have two travel loggers, TraveLog
and CryoLog.
All of our monitoring systems or loggers operate either
in a stand-alone mode or in conjunction with a PC using
custom Window based software.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SCANLOG
SPECIFICATIONS |
|
|
Mastco's
Scanlog is the heart of our
10 to 80-channel system

Drag mouse over image to view close up of Scanlog
ScanLog
allows you to grow using your existing AlarmLogs and DuaLogs
therefore not
wasting valuable resources when you exceed your AlarmLog
MultiPoint system.
Scanlog
generates both an audible and visual alarm whenever an out-of-limit
condition occurs. No cryptic fault codes or unrecognizable
channel number will appear
since you define both the title and error message.
SCANLOG
INSTALLATION GUIDE
Part I - Central Scanner Installation
& Connection
Part II - Commissioning Guide
Part III -Software Installation & PC Commissioning |
|
|
|
|
|
|
|
|
| System
Capacity |
1/80
Channels |
| Display |
4-line
x 40
Character LCD |
| Resolution |
0.1°
C |
| Accuracy |
+/-0.2°
C |
| Data
Log |
As
Loggers |
| Event
Log |
512
Entries |
| Logging
Interval |
As
Loggers |
| Measurement
Rate |
As
Loggers |
| Channel
Titles |
Set
by User |
| Alarm
Messages |
Set
by User |
| Alarm
Features |
Alarm
Key
Six Alarm Zones |
| Alarm
Delay |
0/99
minutes |
| Data
Security |
Settings
Key
System, Multi-level Password |
| Back-up
Battery |
12V,
Float Charged,
7-Days Capacity |
| Temperature
Range |
-200°
C to +200°
C
(-328°
F to +392°F)
|
| Dimensions |
450
x350 x60mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LOGGERS
SPECIFICATIONS |
|
Our
AlarmLog is a single channel battery powered monitor

Drag
mouse over image to view close up of AlarmLog
AlarmLogs
can be used as either a portable unit or wall mounted.
They may be used independently or up to ten units to create
a MultiPoint system.
A full range of installation accessories make the system
simple to install and easy to expand.

Drag
mouse over image to view close up of DuaLog
The
DuaLog is basically a two-channel AlarmLog without a
LCD display or keypad. The primary advantage is that a
customer
receives a two-channel system for about the same cost
of one AlarmLog.
.
|
|
|
|
|
|
|
|
| AlarmLog
|
Single
Channel |
| DuaLog |
Dual
Channel
(without display) |
| Resolution |
0.1°
C |
| Accuracy |
+/-0.2°
C |
| Data
Log |
3072
Points |
| Event
Log |
100
Entries |
| Logging
Interval |
1/99
minutes |
| Measurement
Rate |
Every
4 Seconds |
| Alarm
Delay |
0/99
minutes |
| Battery
Type |
2X
Alkaline AA |
| Battery
Life |
One
Year |
Temperature
Range |
-200°
C to +200°
C
(-328°
F to +392°F)
|
| Dimensions |
80
x 150 x30mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MSM
SPECIFICATIONS |
|
|
MSM
"Our Largest System"

Drag
mouse over image to view close up of MSM
Our
MSM system consists of two basic components, the Central
Scanner
and Remote Sensor Units (RSUs). The Central Scanner continually
monitors each
RSU and maintains all channel history. The large six-line
vacuum fluorescent display (VFD) shows precisely what
the status is at each RSU location
The
MSM and ScanLog systems have many of the same features
since
ScanLog was developed from the MSM system.
|
|
|
|
|
|
|
|
|
| System
Capacity |
90/360
Channels |
| Display |
6-line
x 40
Character VFD |
| Resolution |
0.1°
C |
| Accuracy |
+/-0.2°
C |
| Data
Log |
1984
Points |
| Event
Log |
250
|
| Logging
Interval |
1/6
minutes |
| Measurement
Rate |
9
Sensors a Second |
| Channel
Titles |
Set
by User |
| Alarm
Messages |
Set
by User |
| Alarm
Features |
Alarm
Key
Ten Alarm Zones |
| Alarm
Delay |
0/99
minutes |
| Data
Security |
Settings
Key
System, Multi-level Password |
| Back-up
Battery |
18V,
Float Charged,
6 Hour Capacity |
| Temperature
Range |
-200°
C to +200°
C
(-328°
F to +392°F)
|
| Dimensions |
480
x320 x250mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Our
Travel Temperature Logger |
|
|
|
|
|
TravelLog
is ideal for transit temperature monitoring applications
and was designed with simplicity in mind. It combines cost-effective
data logging with a visual out-of-limits indication using
red and green LEDs. The green LED will continue to flash
while temperatures are within the preset range. If temperatures
go beyond their preset range the red LED will flash a warning
of this out-of-limit condition. TraveLog has a operating
temperature range of -50° C to + 70°
C (-59° F to + 158°
F). |
|
 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mastco's
Cryogenic Travel Logger |
|
|
|
|
|
CryoLog
was designed for shipments with dry ice but can be used
in various applications. The logger is attached on the external
surface of shipping containers with the PTFE probe inside
next to your valuable shipment. CryoLog has three LED indicators
(Normal, Warning and Alarm) for safeguard and ease of detecting
problems during transport. Many other features are similar
to AlarmLog including Mastco's quality and dependability.
CryoLog's operating range is -100°
C to +20°
C (-148°
F to +68°
F).
|
|
|
 |
|
|
|
|
Quality
is Reliability
ISO 9001 registration covers the design and manufacture
of our Temperature Monitor,
Alarm and Logging System and associated applications software.
A
one-year parts and labor warranty and free telephone support
for the lifetime
of your equipment shows our confidence in our systems.
We include free version
software upgrades for the life of your equipment.
Calibration
and Validation
Mastco
will provide a comprehensive calibration of all channels
to ensure the systems
meets or exceeds all regulatory requirements. Mastco's
Calibration Units are
NIST certified and our PC software will guide the non-technical
user through
the calibration sequence for annual re-certification or
an interim quality check.
Calibration dates are stored within each logger and a
certificate is printed when completed.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |